Voltage Drop Calculator for Copper and Aluminium Cable

Enter the supply voltage, the current, the one-way cable length and the conductor size. The calculator finds the voltage lost along the cable, the percentage drop, the power lost as heat and the smallest conductor for your target drop.

By Adzita Editorial Team · Updated 2026-11-03 · How we build and check our tools

For three-phase, the line-to-line voltage.
The distance from source to load, not the total of both conductors.
A design target you choose. Rules and recommendations vary by code and by application.

How voltage drop is calculated

Every conductor has some resistance, so current flowing through it loses voltage along the way. The resistance of a conductor is R = ρ × L ÷ A, where ρ is the resistivity of the metal, L the length and A the cross-sectional area. Copper is about 17.2 nanohm-meters at 20 °C and aluminium about 28.2, so for the same size aluminium has roughly 64 percent more resistance.

For two-wire DC or single-phase AC, the current passes out and back, so the drop is 2 × I × R over the one-way length. For a balanced three-phase system the line-to-line drop is √3 × I × R. The percentage drop is the lost voltage divided by the supply voltage.

Conductor sizes

Metric cables are labeled by cross-sectional area in square millimeters. American wire gauge (AWG) sizes are defined by a diameter formula, d = 0.005 × 92(36 − n) ÷ 39 inches, so each step of three gauge numbers roughly halves the area. For instance 12 AWG has a diameter of about 2.05 mm and an area close to 3.31 mm², while 10 AWG has about 5.26 mm². The calculator converts AWG to area with the formula, so a size listed here is the plain solid conductor, and stranded cable may differ slightly.

A larger conductor lowers the drop but costs more and is harder to terminate, so the choice balances cost, safety and performance.

Reading the result

Low-voltage circuits, such as 12 V lighting, solar and automotive wiring, suffer most because the same few volts represent a big share of the supply.

Estimating, codes and safety

This tool is for estimating and learning. It checks voltage drop only. Current-carrying capacity, derating for ambient temperature and grouping, short-circuit protection, earthing, and the permitted installation method are separate requirements, and local electrical codes govern all of them. A qualified electrician or engineer must design and approve a real installation. An undersized cable can overheat and start a fire even if its voltage drop looks acceptable, so never choose a cable from this result alone.

Worked example

A 15 A load 100 ft from a 120 V single-phase supply, wired in 12 AWG copper.

Inputs

SystemAC single-phase (two conductors)
Supply voltage120 V
Load current15 A
UnitsImperial (feet, AWG)
One-way cable length (feet or meters)100
Conductor size (AWG)12 AWG
Conductor materialCopper (17.2 nΩ·m at 20 °C)
Target maximum drop3 %

Result

4.75 V lost (3.96%)

Voltage at the load: 115.25 V.

The drop is above your target of 3%. Use a larger conductor or a shorter run.

Conductor area3.31 mm²
Resistance per meter5.198 mΩ/m
Voltage drop4.753 V
Drop as % of supply3.96%
Power lost as heat71.3 W
Area needed for a 3% drop4.37 mm²

Estimating note: Quantities and ratings here are estimates for planning and learning. Products, local codes and site conditions differ, so check manufacturer data and local regulations, and use a qualified professional for electrical, structural or safety-critical work.

Frequently asked questions

How do I calculate voltage drop?

Multiply twice the current by the one-way length and the conductor resistance per unit length for a two-wire circuit. For three-phase use √3 instead of 2. Divide by supply voltage for the percentage.

What voltage drop is acceptable?

It depends on the code and the application. A few percent is a common design goal, but the limit that applies to your project comes from local regulations and the equipment maker.

Is aluminium worse than copper for voltage drop?

Aluminium has higher resistivity, so for equal size it drops about 64 percent more voltage. It is often used in larger, lighter feeders with a bigger cross-section to compensate.

Does the calculator account for temperature?

Resistance is taken at 20 °C. Conductors run hotter in practice, which raises resistance and drop, so treat the figure as a lower bound for heavily loaded cables.

Why is the length one-way?

The calculator automatically doubles it for two-wire circuits to include both the outgoing and return conductors, so you only need the distance from source to load.

Watts, Amps and Volts CalculatorConvert between watts, amps and volts for DC, single-phase AC and three-phase AC with power factor.Ohm's Law CalculatorEnter any two of V, I, R and P to solve the other two with Ohm's law and the power law.Battery Life CalculatorEstimate battery runtime from capacity, voltage, load, usable depth of discharge and efficiency.Horsepower CalculatorHorsepower, torque or rpm from the other two, plus hp, PS, kW and watt conversions.